CPSC, Weil-McLain Announce Recall of Ultra 155 & 230 Gas Boilers
Estimated risk
CPSC doesn't classify recalls by risk, so Recall Relay estimated the risk as high from the hazard description. This is our estimate, not an official classification.
- Hazard
- Weil-McLain has determined that the gas valve mounting screws on the recalled boilers may have not been fully tightened during the assembly process and may have come loose in transportation. Weil-McLain is concerned that loose gas fittings could result in leaking gas, fire and/or explosions, that could cause bodily injuries or property damage.
- What to do
- Weil-McLain is providing distributors and installers with a "Safety Notice" package for each boiler containing instructions, replacement screws and a reimbursement form. Installers are also asked to tighten the gas valve union. Installers will be reimbursed $50 for each boiler they inspect.
- Products
-
- Ultra 155 & Ultra 230 Gas Boilers
- Companies
- Weil-McLain, The Weil-McLain Company
- Where it was sold
-
Nationally at plumbing and heating wholesale distributors to plumbers and contractors from December 2002 through February 2003 for approximately $4500.
- Units affected
- 1,700
- About this recall
- The Ultra 155 & Ultra 230 Gas Boilers are condensing high-efficient gas-fired boilers for space heating. They have 93% operating efficiency and use a cast aluminum, mono block heat exchanger packaged in a glossy silver/flat black jacket.