Skip to content

All recalls CPSC

CPSCConsumer productsRecalled Status: Ongoing

CPSC, Notifier Announce Recall for Fire Alarm Panels

Highest. risk

Estimated risk

CPSC doesn't classify recalls by risk, so Recall Relay estimated the risk as high from the hazard description. This is our estimate, not an official classification.

Hazard
The AEU can enter a "sleep" mode, where it does not communicate with the system. When this occurs, audible evacuation signals associated with the failed AEU will not operate and building occupants may not be warned of an emergency.
What to do
Notifier will provide an upgraded CPU firmware set for each AM2020 and AFP1010 panel, at no charge.
Products
  • Fire Alarm Control Panel
Company
Notifier
Where it was sold

Notifier distributors nationwide, from January 2000 through May 2002. The list price for the CPU and DIA combination for the model AM2020 is about $6,400, and the list price for the CPU and DIA combination for the model AFP1010 is about $3,370.

Nationwide

Units affected
6,000
About this recall
The fire alarm control panel includes the central processing unit (CPU-2020 and CPU-2) and Display Interface Assembly (DIA-2020 and DIA-2) components of Notifier model AM2020 and AFP1010 fire alarm control panels with date codes from 0100 to 2003 and firmware version 3.0 and 3.01. The date codes appear on the back outer edge of the PC boards.